The DATA documentation

Table: DATA

Technical Data

DescriptionUnitsValue
Height (excl. mounting bracket)mm640
Widthmm490
Depthmm271
Weight (excl. mounting bracket)kg<30
Connections
PositionPrimaries top. All else bottom.
Primary Connections3/4” BSP Female
Distribution Net Return3/4” BSP Female
Cold Water Inlet15mm Compression Female
Hot Water Outlet15mm Compression Male
CH supply3/4” BSP Female
CH Return3/4” BSP Female
Safety Relief Valve15mm Copper Pipe
Primary Circuit
Maximum Supply Temperature˚C85
Minimum Supply Temperature˚C65
Nominal Supply Temperature˚C80
Maximum Return Temperature˚C40
Pressure ClassPN16
Maximal Permissible Differential Pressure*kPa250 Standard - 450 With dp Regulator
Minimal Permissible Differential PressurekPa50
Max.flowl/h1400
Primary Circuit (after dP/security)
Pressure LosskPa20-60
Secondary Circuit CH
Max. outputkW25
Pump (Energy Class A)15-6; 130
Expansion Vesselltr8
Pressure Relief Valvebar3
Maximum Flow Ratel/h720
Secondary Circuit DHW - DATA
Output (@10-55 ˚C)l/min20.5
Output (@10-55 ˚C)kW65
Secondary Circuit DHW - DATA PLUS
Output (@10-55 ˚C)l/min24
Output (@10-55 ˚C)kW75
Pressure ClassPN10
Minimum PressurekPa50
Design Temperature (Cold Water)˚C10
Nominal DHW Temperature˚C55
DHW Temperature Setpoint˚C35-60
Additional Features
Casing MaterialEPP (Expanded Polypropylene)
Maximum Heat LossesW50 (1.2 kWh/day)
Typical Heat Losses (DHW Only, Keep Warm)W25
Keep Warm ModesEconomy & Comfort
Max. Return Temperature During Keep Warm ModeDHW Setpoint -2˚C
Electrical Information
Electrical Supply Info230V 50Hz
Fuse Ratings3 Amp
Sensor DHWNTC 10kOhm @ 25 Degrees

Converted from the Heatweb wiki article “Table: DATA”, last edited 2018-07-09. Under review for the new site.

Talk to an engineer

Tell us about your network and we will come back with a practical next step, usually within one working day.