The DATA documentation

DATA Technical data

DESCRIPTIONDATA
Nominal primary supply temperature80°C
Maximum primary supply temperature85°C
Minimum primary supply temperature55°C *
Nominal DHW supply temperature55°C
DHW Set Range45°C to 60°C
Return Temp Limit Range35°C to 65°C
CH Limit Range30°C to 80°C
Primary connections¾” Female / 18mm
Mains & DHW connections¾” Female / 18mm
Central heating connections¾” Female / 18mm
Pressure relief15mm
Domestic Hot water heat exchanger (DHW)E8LAS‐40
Central heating heat exchanger (CH)E8LAS‐40
Maximal primary differential pressure (without dP regulator)250kPa
Maximal primary differential pressure (with dP regulator)450kPa
Minimal primary differential pressure50kPa **
Pressure class DH circuitPN16
Pressure class CH circuit (3 bar safety valve)PN10
Pressure class DHW circuitPN10
CH Maximum working pressure2.5 Bar
Casing width490mm
Casing height640mm
Casing depth275mm
Casing MaterialEPP Expanded Polypropylene
Maximum Heat Losses50W (1.2 kWh/day)
Typical Heat Losses (DHW Only, Keep Warm)25W
Weight (basic version)24kg ***
Electrical supply info230V 50Hz
Fuse ratings3 Amp
Sensor DHWNTC 10kohm @ 25°C
Keep Warm ModesEconomy / Comfort
Max Return Temperature during Keep Warm ModeDHW Setpoint - 2°C

.* Minimum required DH supply temperature is DHW setpoint + 5°C with a minimum of 55°C. .** Depends on requested DHW output and available DH supply temperature. .*** Unit weight may vary depending on the optional components built into the unit

Converted from the Heatweb wiki article “DATA Technical data”, last edited 2017-11-27. Under review for the new site.

Talk to an engineer

Tell us about your network and we will come back with a practical next step, usually within one working day.