The MECH HIU documentation

Table: MECH

FunctionUnitsValue
Hot Water
Maximum OutputkW31
Pressure LosskPa18
CapacityL/min9
Temperature Range°C35 to 60
Heating
Maximum OutputkW42
Differential Pressure Controller SetpointkPa20
Kvs Valuem³ / Hr2.5
District Heating Circuit
Maximum Flow Temperature°C95
Pressure ClassBarPN10
Minimum Flow Temperature°C70
Maximum Permissible PressurekPa200
Minimum Differential PressurekPa70
Maximum Pressure LosskPa<25
Connections
District Heating FlowG ¾" F
District Heating ReturnG ¾" F
Cold Water SupplyG ¾" F
Hot WaterG ¾" F
Heating FlowG ¾" F
Heating ReturnG ¾" F
Heat Meter (Flow Mounted)G ¾” Swivel Nut (x2) L=110mm
Heat Meter Return Temperature SensorM10 x 1 – into G ½” Adaptor
Dimensions
Heightmm485
Widthmm585
Depthmm265
Weight incl. Pre-plumbing Bracketkg9.5
Weight excl. Pre-plumbing Bracketkg9

(1) The DHW flow capacity depends on the supply temperature, permissible return temperature and pressure of the distribution network. By means of a flow restrictor in the Mains cold water fitting on the plumbing bracket, the maximum DHW flow rate can be tuned to these external factors. (2) The HIU should be mounted on a standard plumbing bracket (Supplied with the Digi Unit).

Converted from the Heatweb wiki article “Table: MECH”, last edited 2016-02-02. Under review for the new site.