Will keep-warm flow fail the HNTAS bypass KPI?

A heat interface unit in keep-warm passes a few litres of network water an hour to stay ready for a tap. The HNTAS bypass flow KPI allows a network less than that per home. Whether the two collide depends on one thing the KPI does not mention: whether the dwelling's heat meter can see the keep-warm flow. This page works through the published test data and proposes a threshold that does not fail a sound network.

November 2026

The short answer

  • Usually not. Of the 25 heat interface units on the BESA test register, 21 deliver keep-warm in short pulses of 14 to 270 litres an hour. A dwelling heat meter registers flow at that rate, so the water is counted as the home's consumption and never reaches the bypass KPI.
  • Sometimes, on its own. Four units hold temperature with a continuous trickle of 2 to 9 litres an hour. That is below the 15 l/h minimum flow of the usual dwelling meter, and at 70 °C supply it is at or below the flow at which the meter starts counting at all. Water the dwelling meters miss appears in the KPI as bypass.
  • The margin is thin either way. The KPI allows 1 % of peak flow. Shared across the homes on a block, that is 1.4 to 2.3 litres an hour each. Mean keep-warm flow in the tests was 1.8 to 3.2 l/h per unit at 70 °C and 4.7 to 8.3 l/h at 55 °C.
  • A threshold that avoids false failures is the design bypass flow, plus 3 % of the flow measured into the network to cover meter tolerance, plus 3 litres an hour for each connection whose meter has not been shown to register the unit's keep-warm flow. In round numbers that is about 1.25 % of peak flow where the meters see keep-warm, and about 3 % where they cannot be shown to.

The rest of this page shows where those numbers come from.

What the KPI measures

The HNTAS KPI for bypass flow on a communal distribution network is CD-KPI-09. The draft technical standard defines it as a balance of two volumes over a month:

bypass flow rate = (volume delivered at the network's initiation point − sum of the volumes consumed at all its termination points) ÷ time

The initiation point is the bulk meter where the communal network starts. The termination points are the heat meters at the homes. The design limit is 1 % of the peak load flow rate, and the draft standard says the same in its design requirements: total bypass flow should be less than 1 % of the flow at peak demand unless a calculation shows more is needed. There is an equivalent KPI for district distribution networks.

The KPI is called bypass flow, but the sum on the page is every litre the termination meters did not record. Three different things land in it:

  1. True bypass. Water that returns to the plant room through a bypass valve at the top of a riser or the end of a branch, without passing a dwelling meter.
  2. Flow a dwelling meter did not register. Water that did pass through a home's heat interface unit and its meter, at a rate too low for the meter to count.
  3. Disagreement between meters. One bulk meter is being compared with the sum of many small ones, and each has a tolerance.

Only the first is a fault in the network. The other two are properties of the metering. A related KPI, the network heat loss, is the same balance in energy and has the same three contents.

The draft standard does expect keep-warm to be metered. It asks for residents to be told that the meter may record heat use when no heating or hot water is being used. It does not ask whether the meter is able to.

What keep-warm flow looks like

The BESA UK HIU test regime includes a keep-warm test: eight hours with no hot water or heating demand, at a 70 °C supply and again at 55 °C, with the primary flow logged throughout. The full report for every registered unit is published. We read all 25 reports on the register in November 2026, which hold 43 keep-warm tests.

From each report we took the mean primary flow from the results table, and read the flow while water is actually moving from the test graph. The graph readings are good to about ±20 %. Units are numbered here, not named; the register itself is linked under Sources.

The average is small

Dot plot of mean keep-warm primary flow per unit: 1.8 to 3.2 litres an hour across 22 tests at 70 °C supply, and 4.7 to 8.3 litres an hour across 21 tests at 55 °C. A shaded band from 1.4 to 2.3 litres an hour marks one per cent of peak flow shared per home.
Mean keep-warm flow in each test, against the KPI's 1 % of peak flow shared per home. Source: BESA HIU test register, full reports, 43 tests.
Supply temperatureTestsMean primary flow per unitMean heat used per unit
70 °C221.8 to 3.2 l/h18 to 38 W
55 °C214.7 to 8.3 l/h19 to 42 W

A cooler network needs more water to hold the same temperature at the unit, so keep-warm flow roughly doubles between 70 °C and 55 °C.

The delivery is not

The mean hides how the water is delivered. The units fall into three groups.

Three flow traces over two hours on the same scale. The large-pulse unit flows at about 80 litres an hour for about a minute every quarter of an hour and is at zero in between. The small-pulse unit ramps to about 30 litres an hour in frequent short bursts. The trickle unit flows continuously at about 7 litres an hour, between the 6 and 15 litre an hour meter minimum lines.
Three units with nearly the same mean flow at 55 °C, delivered three ways. Redrawn from the flow traces in the published test graphs.
PatternUnitsFlow while flowingHow it behaves
Large pulses1353 to 270 l/hA valve opens for a minute or so, at intervals from a few minutes to an hour, then shuts fully.
Small pulses814 to 63 l/hShorter, more frequent bursts, shut in between.
Continuous trickle42 to 9 l/hA valve held slightly open the whole time.
Dot plot on a logarithmic scale of the flow while keep-warm water is moving, for 25 units at 70 °C and 55 °C supply. Large-pulse units sit between 53 and 270 litres an hour, small-pulse units between 14 and 63, trickle units between 2 and 9. Vertical lines mark a meter start-up flow of 2.5 litres an hour and meter minimum flows of 6 and 15 litres an hour.
Flow while keep-warm water is moving, for every unit, against what a dwelling heat meter registers. Where a unit was tested at both temperatures the two readings are joined.

The full table:

UnitKeep-warm patternMean flow at 70 °C (l/h)Mean flow at 55 °C (l/h)Flow while flowing at 70 °C (l/h)Flow while flowing at 55 °C (l/h)
1Large pulses2.96.1270269
2Large pulses–8.3–210
3Large pulses3.25.4136155
4Large pulses3.25.4136155
5Large pulses2.57.2130144
6Large pulses2.25.853121
7Large pulses–5.8–108
8Large pulses3.26.18382
9Large pulses2.25.07879
10Large pulses1.85.07674
11Large pulses1.84.77372
12Large pulses2.97.67169
13Large pulses2.95.06468
14Small pulses2.98.34263
15Small pulses2.5–48–
16Small pulses2.26.51447
17Small pulses3.25.84441
18Small pulses2.56.11641
19Small pulses2.5–35–
20Small pulses3.27.21832
21Small pulses3.26.81930
22Continuous trickle2.95.09.05.0
23Continuous trickle–6.8–6.8
24Continuous trickle2.2–2.2–
25Continuous trickle1.8–1.8–

A dash means the unit was not tested at that temperature. Units 3 and 4 are two models that share one set of results. The same figures, with the heat used in each test, are in a data file (CSV).

What a heat meter can see

A heat meter's flow sensor has three flow rates that matter here.

  • Nominal flow, qp. The size of the meter. Dwelling meters on heat interface units are commonly qp 1.5 m³/h; qp 0.6 and qp 2.5 are also used.
  • Minimum flow, qi. The lowest flow at which the meter is certified to stay within its error limits. It is a fixed fraction of qp, called the dynamic range. At the common 1:100 range a qp 1.5 meter has a minimum of 15 l/h. A 1:250 version of the same meter has a minimum of 6 l/h.
  • Start-up or cut-off flow. Below this the meter counts nothing. Two current ultrasonic dwelling meters we checked give 2.5 l/h and 3 to 5 l/h for the qp 1.5 size. The qp 0.6 size of the first has a 6 l/h minimum and starts at 1 l/h, which is why a smaller meter helps.

Between start-up and minimum the meter counts, but nobody has certified how well. A Swedish study of meter sizing for single houses found that static meters keep registering down to about a quarter of their minimum flow, with errors somewhat beyond the normal limits.

Set against the test data:

Keep-warm deliveryAgainst a qp 1.5 meter, 1:100Result
Large pulses, 53 to 270 l/hWell above the 15 l/h minimumRegistered
Small pulses, 30 to 63 l/hAbove minimumRegistered
Small pulses, 14 to 19 l/h (four units at 70 °C)At the minimumRegistered, at the edge of the certified range
Trickle, 5 to 9 l/hBelow minimum, above start-upCounted, with unknown error
Trickle, 1.8 to 2.2 l/h (two units at 70 °C)Below start-upNot counted

So the hotter the network, the smaller the keep-warm flow, and the more likely a trickle is to fall below the meter altogether.

Pulses have one weakness of their own. They last about a minute, and a battery meter that samples flow only every 30 seconds can misjudge a short burst. Laboratory tests quoted in a Swedish district heating study found some meters with a 30-second sampling time reading flow 14 % low. So the meter's sampling interval matters as well as its range.

Putting the two together

How much is 1 % of peak flow?

The allowance scales with the block. We sized the peak flow of a communal network in the usual way: diversified hot water demand to the Danish standard DS 439, plus 3 kW of heating per home, at a 35 K design temperature drop.

HomesPeak loadPeak flowPeak flow per home1 % of peak, per home
20186 kW4.6 m³/h228 l/h2.3 l/h
40304 kW7.5 m³/h187 l/h1.9 l/h
100625 kW15.3 m³/h153 l/h1.5 l/h
2001,122 kW27.6 m³/h138 l/h1.4 l/h

Larger blocks have more diversity, so less peak flow per home and a tighter allowance. A wider design temperature drop or a lower heating load tightens it further.

What uses the allowance

Take the 40-home block, with 1.9 l/h per home to spend.

What is missing from the dwelling metersLitres an hour per homeShare of the allowance
Keep-warm in pulses, registered0none
Meters disagreeing by 3 % of the flow through them0.4about 20 %
Trickle keep-warm at 55 °C, counted 10 % low0.5 to 0.725 to 35 %
Trickle keep-warm at 55 °C, counted 30 % low1.5 to 2.080 to 105 %
Trickle keep-warm at 70 °C, not counted1.8 to 2.295 to 115 %

The meter line assumes each home draws about 13 l/h averaged over the year (4,000 kWh at a 30 K mean temperature drop) and that the bulk meter and the dwelling meters differ by 3 %. That is one error limit of a class 2 flow sensor. In a government-commissioned laboratory test of heat meters, eight small meters of one size over-read flow by 2.4 % on average, all in the same direction. A bias that way makes the balance smaller, and can hide real bypass behind a result of zero.

Three conclusions follow.

  • On a network whose units pulse and whose meters are sized normally, keep-warm does not touch the KPI. The 1 % is left for real bypass, less about a fifth for meter tolerance.
  • On a network whose units trickle, keep-warm can use the whole allowance with every bypass shut. The network fails the KPI with nothing wrong in the pipework.
  • Even when it is counted, keep-warm is a larger flow than the bypass allowance: 5 to 8 l/h per home at 55 °C against less than 2. The KPI does not see it, because it is recorded as consumption. It shows in the return temperature instead.

The heat loss KPI has the same gap

The communal network heat loss KPI is the same balance in kilowatt-hours, with a limit of 100 W per dwelling in operation. Keep-warm used 18 to 42 W per unit in the tests. Where the dwelling meter does not register the flow it does not register the heat either, and a fifth to two fifths of the heat loss allowance is spent on energy that reached the home.

A bypass around the meter

A Swedish study of 103 district-heated houses ran this same balance over a summer. In July the house meters summed to 955 m³ and the main meter read 1,616 m³: 41 % of the water was unaccounted for. It was about 8 litres an hour per house, steady from April to July. The cause was a temperature-controlled keep-warm bypass fitted outside each house substation, so the water never passed the house meter. The authors ruled out meter error as the main cause. That is the case the KPI is designed to catch, and it shows the size of number a real keep-warm bypass produces.

A threshold that avoids false failures

The KPI should fail a network for bypass and not for its metering. We suggest judging the operating result against a limit built from three parts:

limit = design bypass flow + 3 % of the mean flow measured at the initiation point + 3 l/h for each termination point whose meter has not been shown to register the unit's keep-warm flow

  • Design bypass flow. As now: the designer's figure, no more than 1 % of peak flow without justification.
  • 3 % of measured flow. One class 2 error limit, for comparing a bulk meter with the sum of the dwelling meters.
  • 3 l/h per unproven connection. This covers the cases measured above: a trickle at 70 °C that is not counted (1.8 to 2.2 l/h), or a trickle at 55 °C that is counted well short. It is zero for a connection where the meter's minimum flow is at or below the unit's flow while flowing, taken from the unit's test report, or where a site check shows the meter counting with heating and hot water off.

For the 40-home block:

NetworkLimit per homeAs a share of peak flow
Meters register keep-warm1.9 + 0.4 = 2.3 l/habout 1.2 %
Meters not shown to register keep-warm1.9 + 0.4 + 3 = 5.3 l/habout 2.8 %

Across blocks of 20 to 200 homes the two cases come to about 1.25 % and about 3 % of peak flow.

Two further rules would stop most nuisance results.

  • Fail on two consecutive months, not one. A monthly volume balance moves with missed readings and with readings taken at different times. One month over the limit is a prompt to look; two is a finding.
  • Treat a clearly negative balance as a metering fault. If the dwelling meters add up to more than the bulk meter by more than the 3 %, the result is not a pass. It says the meters disagree, and it should be reported that way.

It would also help to name the KPI for what it measures: flow not accounted for at the termination points. Bypass is one cause.

What to do on a real network

At design. State the keep-warm flow of the chosen unit, as flow while flowing and not only as an average, and choose a dwelling meter whose minimum flow is below it. A pulsing unit with a standard 1:100 meter meets this. A trickle unit needs a 1:250 meter, or a smaller one, to have a chance.

At commissioning. The draft standard already asks for bypass flows to be demonstrated at minimum demand. Do it with numbers: with heating and hot water off across the block, read the bulk meter's flow and the sum of the dwelling meters over the same hour. The bulk reading is keep-warm plus bypass. The difference between the two is bypass plus whatever the dwelling meters cannot see.

In operation. Look at the balance in the small hours as well as over the month. A night-time gap that matches the number of homes multiplied by a few litres an hour is keep-warm the meters are missing. A gap that does not scale with homes is a bypass.

Limits of this analysis

  • The keep-warm figures are laboratory tests of new units at their manufacturers' settings. Site settings, wear and network pressure change them.
  • The register holds units tested to the current regime. Most installed units are older, and many older units hold temperature with a thermostatic valve that trickles. We have no comparable published data for those.
  • Flow while flowing was read from graphs, to about ±20 %.
  • The peak flows are our sizing of typical blocks, not measurements.
  • No published study that we could find measures how much keep-warm flow dwelling meters miss on a working network. The step from "below the meter's minimum" to "this many litres uncounted" is the weakest in the chain, and it is the one a site test would settle.

Sources

The KPI definitions, with their monitoring points and thresholds, are published openly at hnqap.org. This point is raised there for comment against the bypass flow KPI, as issue 7; results from working networks are welcome. Related reading: heat meters and heat network monitoring and HNTAS KPIs.

Check a network before it is assessed

If you have a communal network with dwelling heat meters and a bulk meter, we can run this balance on your own data and tell you how much of the unaccounted flow is bypass and how much is metering.