td { padding: 4px; }

ItemThermal IntegrationThermal IntegrationAltecnicPeglerEvinoxWilson KamoSAV
VWART Temperature23.248.84744.643.6Failed34.5
VWART Volume77.4207.1191.6167.5144.1Failed116.7
Time to 42C215221141193
Time to 50C (HSE guidelines <60s to tap)2663017765823
Time to 55C (HSE guidelines for care homes <60s to tap)2884828858191
Failed TestsTest 6 - Low Flow Hot Water: The HIU could not produce DHW at 0.02 l/sFailed to achieve 70C in space heating tests

Converted from the Heatweb wiki article “HIU Test Comparison”, last edited 2020-10-02. Under review for the new site.