Function Units Value
Hot Water  
Maximum Output  kW 31
Pressure Loss  kPa 18
Capacity  L/min 9
Temperature Range  °C 35 to 60
Heating
Maximum Output  kW 42
Differential Pressure Controller Setpoint kPa 20
Kvs Value m³ / Hr 2.5
District Heating Circuit  
Maximum Flow Temperature  °C 95
Pressure Class  Bar PN10
Minimum Flow Temperature  °C 70
Maximum Permissible Pressure  kPa 200
Minimum Differential Pressure  kPa 70
Maximum Pressure Loss  kPa <25
Connections
District Heating Flow G ¾" F
District Heating Return G ¾" F
Cold Water Supply G ¾" F
Hot Water G ¾" F
Heating Flow G ¾" F
Heating Return G ¾" F
Heat Meter (Flow Mounted) G ¾” Swivel Nut (x2) L=110mm
Heat Meter Return Temperature Sensor M10 x 1 – into G ½” Adaptor
Dimensions
Height mm 485
Width mm 585
Depth mm 265
Weight incl. Pre-plumbing Bracket kg 9.5
Weight excl. Pre-plumbing Bracket kg 9