Diversity
Danish
https://docs.google.com/spreadsheets/d/1TtprDWpiO6NmWu6S8g5v00gYaIJC5v9B30qqNb8nUSw/edit?usp=sharing
Studies
Live Anonymous Diversity
https://heatweb.fred.sensetecnic.com/api/public/graph/dhwload
This data provides 3 variables as standard, in one second resolution:
- DHW flow rate (litres/minute)
- DHW Power delivered (kW) based on mains at 10C and recorded output temperature
- How many systems running
Ways to Reduce Peak Load
- Shift heating load.
- Keep heating constant,
- Heating on earlier on the coldest days (optimum start), to avoid morning surge.
- Hot water cylinder.
- Set peak rate costs, from 7:30 to 8:30 on cold Winter weekdays.
- Peak rate on/off indicated to user so they can choose to avoid a peak rate time. No charge for draw-offs that start in cheap rate but continue into peak.
- Option to have heating linked to auto-off during peak times.
- Option to reduce DHW temperature at peak. Doesn't reduce load, but increases primary dT (reduces flow).
1st Diversity Field Trial
Below are three screen shots from two days in a row (days 8 & 9) of the total DHW loads from the 2 bed system been used to examine diversity for a retired couple.
The reason for posting it is, it demonstrates the theory nicely. You can spot the additional load from yesterday, with a new peak just after the highest peak. The peaks last approx 4 seconds each and are 10 minutes apart.
9 days of data - or 9 HIUs - gives a peak of 52kW against a potential peak of 342kW if all HIUs drew 38kW at the same time. Danish diversity gives 85kW. But this is too few HIUs to define a standard from.
If we want diversity up to say 1000 properties, then the proposition is:
Monitor 10 HIUs for 100 days gives you 1000 days of data from which you can create a standard for UK diversity, that is more relevant than the Danish standard referred to in guidance (but not yet translated into English).
Live system on http://heatweb.ddns.net:1881/diversity